SD1 Series Inverters Function Parameters
-79-
Name Description Default Modify
(The max. frequency)
P08.36
Amplitude
value for
frequency
arrival
detection
When the output frequency is among the below
or above range of the set frequency, the
multi-
function digital output terminal will output
the signal of "frequency arrival", see the diagram
below for detailed information:
Y,
RO1, RO2
Output frequency
t
Setting
frequency
P08.36
t
P08.36
Setting range: 0.00Hz~P00.03 (the max.
0.00Hz ○
P08.37
Energy
consumption
brake enable
This parameter is used to control the internal
braking unit.
0: Disabled
1: Enabled
Note: It is only applicable to inverter
models that
are built in braking units.
0 ○
P08.38
Energy
consumption
brake
threshold
voltage
After setting the original bus voltage to brake the
energy, adjust the voltage appropriately to brake
the load. The
factory changes with the voltage
level.
Setting range: 200.0~2000.0V
To prevent setting the value too high, set per
recommended setting range in table below:
/230V
:
○
:
For 460V
inverters:
740.0V
P08.39
Cooling fan
running mode
0: Common running mode
1: Keeps running after being powered on
2: Runs when the inverter
ramp frequency is no
less than 0 Hz, and the inverter output current is
0 ○