SD1 Series Inverters Function Parameters
-82-
Name Description Default Modify
P08.46
DOWN
terminal
frequency
decrement
integral speed
0.01~50.00s 0.50 s
○
P08.47
Action
selection at
power loss
Ones place: Action of the digital regulation
frequency at power off.
0: Save when power off
1: Clear when power off
Tens place: Action of the set Modbus frequency
at power off
0: Save when power off
1: Clear when power off
Hundreds place: Action of the other
communication frequencies at power off
0: Save when power off
0x000
○
P08.48
High bit of
consumption
This parameter is used to set the original value of
the power consumption.
The original value of the power consumption =
(P08.48×1000+ P08.49) kWh
Setting range of P08.48: 0~59999
Setting range of P08.49: 0.0~999.9
0
○
P08.49
Low bit of
original power
consumption
0.0
○
P08.50
Flux brake
coefficient
This function code is used to enable magnetic
flux.
0: Invalid.
100~
150: the bigger the coefficient, the bigger
the braking strength.
This inverter
can slow down the motor by
increasing the magnetic flux. The energy
generated by the motor during braking
can be
transformed into heat energy by increasing the
magnetic flux.
The inverter
monitors the state of the motor
continuously even during magnetic flux period.
0
○