SD1 Series Inverters Function Parameters
-92-
Name Description Default Modify
frequency at P11.02, to make the inverter
generate power again. The returning power can
maintain the bus voltage to ensure a rated
running of the inverter
power.
400V 460V 660V
Frequency
decrease
point at
sudden
240V 460V 530V 800V
Note:
Adjust the parameter properly to avoid the
stopping caused by inverter
the switching of the grid.
Prohibit the input phase loss protection to
enable this function.
P11.03
Overvoltage
stall protection
0: Disabled
1: Enabled
DC bus voltage
Overvoltage stall
point
Output frequency
1
○
P11.04
Overvoltage
voltage
110~150% (standard bus voltage) (400V) 130%
○
110~150% (standard bus voltage)
(220/230/460V)
120%
P11.05
Current limit
The actual increasing ratio is less than the ratio
of output frequency because of the big load
during accelerated
running. It is necessary to
take measures to avoid overcurrent fault and the
inverter trips.
During the running of the inverter, this function
will detect the output current and compare it with
the limit level defined in P11.06. If it exceeds the
0x01
◎
P11.06
Automatic
current limit
level
G:
160.0%
◎
P11.07
Frequency-
drop rate
10.00
Hz/s
◎