EasyManua.ls Logo

INVT Goodrive350 IP55

INVT Goodrive350 IP55
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-166-
Function
code
Name
Description
Default
value
Modify
Set frequency f
Time t
Jump
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Setting range: 0.00HzP00.03 (max. output
frequency)
P08.15
Amplitude of
wobbling
frequency
0.0100.0% (relative to set frequency)
0.0%
P08.16
Amplitude of
jump frequency
0.050.0% (relative to amplitude of wobbling
frequency)
0.0%
P08.17
Rise time of
wobbling
frequency
0.13600.0s
5.0s
P08.18
Descend time of
wobbling
frequency
0.13600.0s
5.0s
P08.19
Switching
frequency of
acceleration/dec
eleration time
0.00P00.03 (max. output frequency)
0.00Hz: no switch-over
Switch to acceleration/deceleration time 2 if the
running frequency is larger than P08.19
0.00Hz
P08.20
Frequency
threshold of the
start of droop
control
0.0050.00Hz
2.00Hz
P08.21
Reference
frequency of
acceleration/dec
eleration time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight acceleration/deceleration
only.
0
P08.22
Reserved
/
/
/
P08.23
Number of
decimal points of
frequency
0: Two decimal points
1: One decimal point
0
P08.24
Number of
decimal points of
linear speed
0: No decimal point
1: One
2: Two
3: Three
0
P08.25
Set count value
P08.2665535
0

Table of Contents