Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-167-
Automatic fault
reset times
Automatic fault reset times: When the VFD
selects automatic fault reset, it is used to set the
times of automatic reset, if the continuous reset
times exceeds the value set by P08.29, the VFD
will report fault and stop to wait for repair.
Interval of automatic fault reset: select the
interval time from when fault occurred to
automatic fault reset actions.
After VFD starts, if no fault occurred during 60s,
the fault reset times will be zeroed out.
Setting range of P08.28: 0–10
Setting range of P08.29: 0.1–3600.0s
Automatic fault
reset time
interval
Reduction ratio
of droop control
This function code sets the variation rate of the
VFD output frequency based on the load; it is
mainly used in balancing the power when
multiple motors drive the same load.
Setting range: 0.00–50.00Hz
Switch-over
between motor 1
and motor 2
0x00–0x14
Ones: Switch-over channel
0: Switch over by terminal
1: Switch over by Modbus/Modbus TCP
communication
2: Switch over by
PROFIBUS/CANopen/DeviceNet
3: Switch over by Ethernet communication
4: Switch over by
EtherCAT/PROFITNET/Ethernet IP
communication
Tens: Motor switch over during running
0: Disable switch over during running
1: Enable switch over during running
FDT1 level
detection value
When the output frequency exceeds the
corresponding frequency of FDT level,
multi-function digital output terminal outputs
"frequency level detection FDT" signal, this
signal will be valid until the output frequency
lowers to below the corresponding frequency
(FDT level-FDT lag detection value), the
waveform is shown in the figure below.
FDT2 level
detection value