Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-168-
Function
code
Name
Description
Default
value
Modify
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
Setting range of P08.32: 0.00HzP00.03 (max.
output frequency)
Setting range of P08.33: 0.0100.0% (FDT1
level)
Setting range of P08.34: 0.00HzP00.03 (max.
output frequency)
Setting range of P08.35: 0.0100.0% (FDT2
level)
P08.36
Detection value
for frequency
arrival
When the output frequency is within the positive
/negative detection range of the set frequency,
the multi-function digital output terminal outputs
"frequency arrival" signal as shown below.
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00HzP00.03 (max. output
frequency)
0.00Hz
P08.37
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
1
P08.38
Energy-
consumption
brake threshold
voltage
Set the starting bus voltage of
energy-consumption brake, adjust this value
properly can brake the load effectively. The
default value will change with the change of
voltage class.
Setting range: 200.02000.0V
220V
voltage:
380.0V;
380V
voltage:
700.0V;
P08.39
Running mode
of cooling fan
0: Common running mode
1: The fan keeps running after power up
2. Running mode 2
0