Figure 23: Clearance Requirements for Airow and Hardware Maintenance for a QFX5240 Switch
• For the cooling system to funcon properly, the airow around the chassis must be unrestricted. See
"QFX5240 Cooling System" on page 32 for more informaon about the airow through the chassis.
• If you are mounng a QFX5240 in a rack with other equipment, ensure that the exhaust from other
equipment does not blow into the intake vents of the chassis.
• Leave at least 24 in. (61 cm) both in front of and behind the QFX5240. For service personnel to
remove and install hardware components, you must leave adequate space at the front and back of
the switch. NEBS GR-63 recommends that you allow at least 30 in. (76.2 cm) in front of the rack and
24 in. (61 cm) behind the rack.
Site Electrical Wiring Guidelines
Table 14 on page 44 describes the factors you must consider while planning the electrical wiring at
your site.
WARNING: You must provide a properly grounded and shielded environment and use
electrical surge-suppression devices.
Averssement Vous devez établir un environnement protégé et convenablement mis à
la terre et uliser des disposifs de parasurtension.