Protective functions
© KEB, 2012-10 COMBIVERT F5-A, -E, -H Page 7.13 - 43
7
Pn.93: Flow monitor input selection
Bit
-No.
Decimal value Input Terminal
0 1 (default) ST (prog. input „control release/reset“) X2A.16
1 2 RST (prog. input „reset“) X2A.17
2 4 F (prog. input „forward“) X2A.14
3 8 R (prog. input „reverse“) X2A.15
4 16 I1 (prog. input 1) X2A.10
5 32 I2 (prog. input 2) X2A.11
6 64 I3 (prog. input 3) X2A.12
7 128 I4 (prog. input 4) X2A.13
8 256 IA (internal input A) no
9 512 IB (internal input B) no
10 1024 IC (internal input C) no
11 2048 ID (internal input D) no
Pn.94: Flow monitoring warning delay time
Bit
-No.
Meaning
0 0: off (default)
The reaction time of 0 (off)... 60.00 s of valve / ow monitor is adju-
sted here. (default value: 0 (off).
Pn.95: Flow monitoring minimum temperature
Denes the temperature limit in the range of 0...90 ° C, condensation risk.
All parameters are not set-programmable.