7.3 AKD Fault
For most AKD Faults, refer to the Fault and Warning Messages table in the AKD Installation Manual for fur-
ther explanation and possible remedies.
7.3.1 Fieldbus Fault – F702
AKD F702 Fault is set if communication between the drive and controller is lost. The primary cause of this
fault is a communication timeout between the drive and controller. The controller is responsible for setting the
Requested Packet Interval rate at which cyclic messages are exchanged between the drive and control. If the
rate is set too short, communication may timeout. 10ms is the fastest support rate for EtherNet/IP on AKD.
For simultaneous operation of Workbench and EtherNet/IP communications, the rate should be reduced to
20ms.