BetrHbKRC2FL--USA--Fehler 11.04.00 en
10.1.13 Error messages valid for the KSDs
(valid from Firmware V0.3 onwards)
IBS trip number Lecom error
number
Message text Meaning
0 0 “ok” Device state OK
1 72 “Pr1--Trip Checksum error in parameter set 1
3 105 “HO5--Trip” Checksum error in the control unit device set
5 71 “CCr--Trip” Microcontroller crash
6 11 “OC1--Trip” Power unit overcurrent (short--circuit or ground
fault), hardware monitoring
7 12 “OC2--Trip” Short--circuit, software monitoring
8 15 “OC5--Trip” I*t overload
10 50 “OH--Trip” Overtemperature, heat sink
11 91 “EEr--Trip” External error, short--circuit braking requested by
the controller
19 32 “LP1--Trip” Motor phase failure
24 79 “Pr5--Trip Communication error with the EEPROM in the
control unit
28 65 “CE4--Trip” Max. permissible number of communication errors
with the drive bus exceeded, or too many toggle
bit errors in succession, causes short--circuit
braking.
43 80 “PR6--Trip” Communication error with the EEPROM in the
power unit
44 106 HO6 trip Checksum error in the power unit device set