Starting up the device – Basic configuration
Leuze electronic GmbH + Co. KG BPS 348i 68
Parameter Rel.
addr.
Data
type
Value
range
Default Unit Explanation
Metr. Inch
Output Event for activating the output.
The individual functions are
OR-linked to one another.
1.0 Bit 0…1 0 ------------- Position limit value1:
If the position value lies out-
side of configured Limit value
range1, the output is set:
0: OFF
1: ON
1.1 Bit 0…1 0 ------------- Position limit value2:
If the position value lies out-
side of configured Limit value
range2, the output is set:
0: OFF
1: ON
1.2 Bit 0…1 0 ------------- Speed limit value:
If the speed value lies outside
of the configured values, the
output is set.
0: OFF
1: ON
1.3 Bit 0…1 0 ------------- Position value invalid:
If no valid position value can
be ascertained because, e.g.,
no barcode tape is read or the
barcodes are destroyed or
soiled, the output is set.
0: OFF
1: ON
1.4 Bit 0…1 0 ------------- Speed value invalid:
The output is set if no valid
speed can be calculated.
0: OFF
1: ON