Vertiv
™
| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 6
1.4.1 Moving the Cabinets
The route to be traveled between the point of arrival and the unit’s position must be planned to make sure that
all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check
that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of
corridors).
Ensure that the UPS weight is within the designated surface weight loading (lb/in
2
) of any handling equipment.
For weight details, see Table 13.
The UPS can be handled with a forklift or similar equipment. Ensure any lifting equipment used in moving the
UPS cabinet has sufficient lifting capacity. When moving the unit by forklift, care must be taken to protect the
panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are
completely beneath the unit.
Handling with straps is not authorized.
1.4.2 Clearances
The Liebert EXL has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of
the equipment should be sufficient to permit free passage of personnel with the doors fully opened. It is
important to leave a distance of 24in. (610mm) between the top of the UPS and any overhead obstacles to allow
the module to be serviced and to permit adequate circulation of air coming out of the unit.
1.4.3 Raised-Floor Installations
If the equipment is to be located on a raised floor, it should be mounted on a pedestal suitably designed to
accept the equipment point loading. Refer to Figure 20 to design this pedestal.
1.4.4 Kick Plate Installation
If the unit is to be installed in a position that does not permit access to rear kick plates, then the kick plates
should be installed before the unit is placed in its final position.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Because the weight distribution in the cabinet is uneven, use extreme care while handling and
transporting. Take extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel.
The UPS module weighs up to 8095 lb. (3672 kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift
and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
AVERTISSEMENT
Le centre de gravité élevé de l’appareil présente un risque de renversement. Une mauvaise manutention
peut entraîner des dommages matériels, des blessures et même la mort.
En raison de la distribution inégale du poids de l’armoire, vous devez faire preuve d’extrême prudence lors
de sa manipulation et de son transport. Faites preuve d’une extrême prudence lors de la manutention des
armoires ASC afin d’éviter de les endommager ou de blesser le personnel.
Le module ASC pèse jusqu’à 3 672 kg (8 095 lb).
Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant de manipuler
chaque armoire. Testez le levage et l’équilibre les armoires avant de transporter l’appareil. Maintenez en
tout temps l'inclinaison verticale minimale.