| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 25
Table 6 Rectifier Input Breaker specifications
Power
Class
kAIC
rating
RIB Specification
RIB General
Specification
Comments
625-
800kVA
65kA
Module
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066
(Low Voltage AC Power Circuit Breaker), which are
required for use in UL-listed switchgear or switchboards.
The circuit breaker must have a short-time rating of 65kA
at a maximum voltage of 480V for three cycles.
The remote breaker must be
equipped with UVR and
auxiliary contacts for proper
operation with the UPS.
No UPS internal fuse
protection on
rectifier and bypass
input.
100kA
Module
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066
(Low Voltage AC Power Circuit Breaker), which are
required for use in UL-listed switchgear or switchboards.
The circuit breaker must have a short-time rating of
100kA at a maximum voltage of 480V for three cycles.
No UPS internal fuse
protection on the
rectifier input. The
bypass input has
fuse protection.
1000-
1200kVA
65kA
Module
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066
(Low Voltage AC Power Circuit Breaker), which are
required for use in UL-listed switchgear or switchboards.
The circuit breaker must have a short-time rating of 65kA
at a maximum voltage of 480V for three cycles.
The remote breaker must be
equipped with UVR and
auxiliary contacts for proper
operation with the UPS.
No UPS internal fuse
protection on
rectifier and bypass
input.
100kA
Module
UL-Listed 489 (Molded Case Circuit Breaker) or UL 1066
(Low Voltage AC Power Circuit Breaker), which are
required for use in UL-listed switchgear or switchboards.
The circuit breaker must have a short-time rating of
100kA at a maximum voltage of 480V for three cycles.
UPS internal fuse
protection exists on
rectifier and bypass
input.
Table 7 Rectifier Input Breaker contacts
Item
Terminal
Block Pin
Connect to
(Description of External Item)
Not Used
TB6 1 Not Used
TB6 2 Not Used
Not Used
TB6 3 Not Used
TB6 4 Not Used
Not Used
TB6 5 Not Used
TB6 6 Not Used
Not Used TB6 7 Not Used
Breaker Motor Operation TB6 8 Motor Operation Enable (240VAC)
Not Used TB6 9 Not Used
Breaker Motor Operation TB6 10 Motor Operation Close Coil
Breaker Auxiliary Status
TB7 1 RIB Aux Status Common
TB7 2 RIB Aux Status, Normally Closed Contact, Closed = CB is Open
TB7 3 RIB Aux Status, Normally Open Contact, Open = CB is Open
Breaker UVR Control
TB7 4 RIB UVR Return
TB7 5 RIB UVR +48VDC
1. For TB7, Pins 1-3, each contact has:
Maximum voltage: 24VDC
Maximum current: 10mA
Wire range: #14-22AWG
Maximum length: 500 ft. (150m)
2. All external wire field-supplied.
3. All wiring must be in accordance with national and local electrical codes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert EXL and is the answer not in the manual?

Liebert EXL Specifications

General IconGeneral
Frequency50/60 Hz
Operating Temperature0°C to 40°C
EfficiencyUp to 99%
Input Voltage480V
Output Voltage480V
TopologyDouble Conversion
Form FactorTower
Battery TypeVRLA, Lithium-ion
Communication InterfaceRS-232, USB
Humidity0-95% non-condensing

Related product manuals