| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 28
3.5 COMMUNICATION AND MONITORING
The Liebert EXL has these monitoring options:
Liebert IntelliSlot
®
Unity-DP (Dual Protocol) Card
The Liebert IntelliSlot Unity Card provides Web, embedded Vertiv
®
LIFE
Technology, Vertiv Protocol, SNMP, BACnet
IP/MSTP, Modbus TCP/RTU, SMTP, SMS, and telnet communication and control capabilities in one unified communication
platform. The platform supports 10/100 Mbit Ethernet, IPv4 and IPv6, HTTP/HTTPS for device Web page access, SMTP
interface for e-mail, SMS interface for text messaging, Vertiv Protocol for communicating with Trellis
and Liebert Nform
®
software applications and LIFE technology for supporting Liebert Remote Service Delivery.
SNMP v1/v2c/v3, Modbus TCP/IP, BACnet IP, Modbus RTU, BACnet MSTP and YDN23 third-party protocols are also supported
for building management and network management applications. The Liebert IntelliSlot Unity card provides ground fault
isolated 10/100 baseT Ethernet and RS-485 network connectivity.
Programmable Relay Board
Input Contact Isolator Board
Figure 13 Terminal block locations—input cabinet
3.5.1 Alber
®
Monitoring System
The matching Liebert EXL Battery Cabinet has space for an Alber battery monitoring system. The battery
monitoring system can be factory-installed or field-installed later.
The Alber Battery Monitor by Vertiv continuously checks all critical battery parameters, such as cell voltage,
overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery
will verify the battery’s operating integrity. Capabilities include automatic internal patented DC resistance tests
and trend analysis, providing the ability to analyze performance, aid in troubleshooting and detect failing cells
before they fail.
Terminal blocks are inside the
control drawer in the
Liebert EXL’s input cabinet.
See Figure 14 or 15 for the
drawer’s location.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert EXL and is the answer not in the manual?

Liebert EXL Specifications

General IconGeneral
Frequency50/60 Hz
Operating Temperature0°C to 40°C
EfficiencyUp to 99%
Input Voltage480V
Output Voltage480V
TopologyDouble Conversion
Form FactorTower
Battery TypeVRLA, Lithium-ion
Communication InterfaceRS-232, USB