| Liebert® EXL™ 625-1100kVA Installation Manual | Rev. 3 | 02/17 2
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel.
The UPS module weight is up to 8095 lb. (3672 kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift
and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
Slots at the base of the module cabinets are intended for forklift use. Base slots will support the unit only
if the forks are completely beneath the unit.
Read all of the following instructions before attempting to move, lift, or remove packaging from unit, or
prepare unit for installation.
AVERTISSEMENT
Le centre de gravité élevé de l’appareil présente un risque de renversement. Une mauvaise manutention
peut entraîner des dommages matériels, des blessures et même la mort.
Faites preuve d’une extrême prudence lors de la manutention des armoires ASC afin d’éviter de les
endommager ou de blesser le personnel. Le module ASC pèse jusqu’à 3 672 kg (8 095 lb).
Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant de manipuler
chaque armoire. Testez le levage et l’équilibre des armoires avant de transporter l’appareil. Maintenez en
tout temps l'inclinaison verticale minimale.
Les fentes situées à la base des armoires du module sont conçues pour utiliser le chariot élévateur. Les
fentes situées à la base peuvent soutenir le système seulement si les fourches se trouvent complètement
sous le système.
Lisez toutes les instructions ci-dessous avant de tenter de déplacer, lever, déballer ou préparer le
système en vue de son installation.
WARNING
Risk of electrical shock and fire. Can cause equipment damage, personal injury or death.
Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The
area around the UPS system should be kept free of puddles of water, excess moisture and debris.
Only test equipment designed for troubleshooting should be used. This is particularly true for
oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or
using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at
the capacitor banks and at the DC connections.
All wiring must be installed by a properly trained and qualified electrician. All power and control wiring
must comply with all applicable national, state and local codes.
One person should never work alone, even if all power is disconnected from the equipment. A second
person should be standing by to assist and to summon help in case of an accident.