38 TM1700-SERIES ZP-BL16E BL1448GE
4 CABA LOCAL
Label names
In the graph window the recordings have a label for
identification.
The label names in the graph view and parameter
view are abbreviated. The first character shows the
measured quantity, the rest of the label name is the
object ID.
General text object ID
CIR Operation coil circuit
CMD Command, control pulse
T Trip
C Close (note C is also used for phase C)
M Main contact timing
R Resistor contact timing (not R is also used for right
part of Head)
R Right part of head
L Left part of head
Head naming is a way of naming the breaking cham-
bers on a general stand/structure.
A Phase A
B Phase B
C Phase C
The first character in the label name
Current I
Voltage V
Angle w
Motion M
Resistance R
Time t
Velocity v
Acceleration a
Object ID list
[n] - the letter n stand for a digit, 0 - 9
Object ID Explanation
CIR[n] Common phase, close&trip coil current
circuit [n]
A CIR[n] Phase A, close&trip coil current circuit [n]
B CIR[n] Phase B, close&trip coil current circuit [n]
C CIR[n] Phase C, close&trip coil current circuit [n]
CCIR[n] Common phase, close coil current circuit
[n]
ACCIR[n] Phase A, close coil current circuit [n]
BCCIR[n] Phase B, close coil current circuit [n]
CCCIR[n] Phase C, close coil current circuit [n]
TCIR[n] Common phase, trip coil current circuit [n]
ATCIR[n] Phase A, trip coil current circuit [n]
BTCIR[n] Phase B, trip coil current circuit [n]
CTCIR[n] Phase C, trip coil current circuit [n]
CMD[n] Common phase, close&trip command [n]
A CMD[n] Phase A, close&trip command [n]
B CMD[n] Phase B, close&trip command [n]
C CMD[n] Phase C, close&trip command [n]
CCMD[n] Common phase, close command [n]
ACCMD[n] Phase A, close command [n]
BCCMD[n] Phase B, close command [n]
CCCMD[n] Phase C, close command [n]
TCMD[n] Common phase, trip command [n]
ATCMD[n] Phase A, trip command [n]
BTCMD[n] Phase B, trip command [n]
CTCMD[n] Phase C, trip command [n]
AUXa[n] Common phase, a-contact [n]
AAUXa[n] Phase A, a-contact [n]
BAUXa[n] Phase B, a-contact [n]
CAUXa[n] Phase C, a-contact [n]
AUXb[n] Common phase, b-contact [n]
AAUXb[n] Phase A, b-contact [n]
BAUXb[n] Phase B, b-contact [n]
CAUXb[n] Phase C, b-contact [n]
- Common phase
A Phase A
B Phase B
C Phase C
A [nn] Phase A, break No. [nn]
B [nn] Phase B, break No. [nn]
C [nn] Phase C, break No. [nn]
A [nn]M Phase A, break No. [nn], main contact
A [nn]R Phase A, break No. [nn], resistor contact
B [nn]M Phase B, break No. [nn], main contact
B [nn]R Phase B, break No. [nn], resistor contact
C [nn]M Phase C, break No. [nn], main contact
C [nn]R Phase C, break No. [nn], resistor contact
A[n] Phase A, head [n]
B[n] Phase B, head [n]
C[n] Phase C, head [n]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megger TM1700 Series and is the answer not in the manual?

Megger TM1700 Series Specifications

General IconGeneral
BrandMegger
ModelTM1700 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals