LEVEL SYSTEM SYNCHRONIZATION
Avoid mounting the DPL+ near another ultrasonic level monitor. Likewise, when more than one monitor is
installed within a single plant/facility, ensure the transducer cables of each system are run in separate
grounded metal conduits. If this system separation is impractical, or despite separation efforts measurement
difficulties are encountered, system synchronization may be required.
To synchronize the DPL+ with an AIRANGER XPL Plus or another DPL+...
1. Mount the level monitors together in one cabinet.
2. Ensure the level monitors share a common power (mains) supply, and ground (earth).
3. Interconnect the SYNC terminals of the level monitors to be synchronized.
To synchronize the DPL+ with other Milltronics ultrasonic
level monitors (not listed) contact Milltronics
or your local distributor.