APPLICATION PARAMETERS
This section identifies the DPL+ operator programmable features which may be used to modify the DPL+
display, failsafe, relay, and/or mA output operation.
VOLUME PARAMETERS (P050 to P055)
If Readings proportional to volume are desired, adjust the following parameters.
If Volume Conversion is not required, proceed to READING PARAMETERS.
P050 TANK SHAPE
Enter the Tank Shape option that matches the vessel monitored.
If the Tank Shape option selected, requires additional vessel dimension entry, the
associated
parameters
(as indicated below) may be scroll accessed.
When Operation is "level" (P001 = 1), material volume is calculated. Alternatively, when
Operation is "space" (P001 = 2), remaining vessel capacity is calculated.
In the RUN mode, Readings are displayed in percent of ( and mA outputs are proportional to )
maximum volume. To convert Readings to volumetric units, see Max Volume (P051).
values: 0 = volume calculation not required (preset)
flat level bottom
half sphere bottom (P052)
1 =
cone / pyramid bottom (P052)
2 =
sphere
Universal Linear (P054 / P055)
Universal Curved (P054 / P055)
8 =
9 =
10 =
flat slope bottom (P052)
4 =
5 =
flat ends
parabola ends (P052 / P053)
6 =
7 =
parabola bottom (P052)
3 =
A
A
L
or
A
A
or
or
A