P203 (V) mA VALUE / TRANSDUCER
View the current value of the mA output associated with the Point Number displayed.
This is the Auxiliary Reading displayed when is pressed in the RUN mode.
If the Point Number is included in a Dual Point Average or Dual Point Difference calculation,
the displayed value represents the average or difference obtained from both vessels.
If both mA outputs are allocated to the same Point Number, the value of mA Output 1
is displayed.
values: 0.000 to 22.00
P210 0/4 mA SETPOINT
Use this feature to reference the minimum mA output to any point in the measurement range.
Enter the material level (referenced to Empty, P006) corresponding to the minimum mA output.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation (P001).
Typically, this value is entered in Units (P005) or percent of Span (P007). If mA Function is set
for "volume", enter the value in the Max Volume (P051) units or in percent of Max Volume.
values: -999 to 9999
P211 20 mA SETPOINT
Use this feature to reference the 20 mA output to any point in the measurement range.
Enter the material level (referenced to Empty, P006) corresponding to 20 mA.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation (P001).
Typically, the value is entered in Units (P005) or percent of Span (P007). If mA Function is set
for "volume", enter the value in the Max Volume (P051) units or as a percent of Max Volume.
values: -999 to 9999
P212 mA MIN LIMIT
Use this feature to prevent the mA output from falling below the minimum acceptable mA
input value (preset to 3.800 mA) of the device connected.
values: 0.000 to 22.00
P213 mA MAX LIMIT
Use this feature to prevent the mA output from exceeding the maximum acceptable mA input
value (preset to 20.20 mA) of the device connected.
values: 0.000 to 22.00
APPLICATION PARAMETERS
PL-508 43