P704 RATE FILTER
Use this feature to avoid Rate Value (P707) fluctuations due to a "splashing" material surface.
This value is automatically altered when Measurement Response (P003) is altered.
See TECHNICAL REFERENCE Measurement Response.
This value automatically alters the Rate Update Time (P705) and / or Rate Update Distance
(P706). Alternatively, these parameter values may be altered independently.
Enter the time period/distance the Rate Value is averaged before display update.
values: 0 = rate display not required
1 = continuously averaged and updated
2 = 1 minute or 50 mm (2 in)
3 = 5 minutes or 100 mm (3.9 in)
4 = 10 minutes or 300 mm (11.8 in)
5 = 10 minutes or 1000 mm (39.4 in)
P705 RATE UPDATE TIME
Enter the time period (in seconds) over which the material level rate of change is averaged
before Rate Value update.
values: 0.000 to 9999
P706 RATE UPDATE DISTANCE
Enter the material level change (in metres) to initiate a Rate Value update.
values: 0.000 to 9999
P707 (V) RATE VALUE
View the rate of material level change (in Units (P005) or % of Span (P007) per minute).
(A negative rate indicates the vessel is emptying).
This is the value displayed when is pressed in the RUN mode.
values: 0.000 to 9999
TECHNICAL REFERENCE
7
PL-508 56