P906 COMMUNICATIONS
to test the DPL+ communications circuitry.
Before activating this feature connect terminal block contacts 27 to 30 and 28 to 31.
On successful test completion, "PASS" is displayed. If "FAIL" is displayed, repeat the test.
(The first test performed sets up the auto polarity function).
P907 PROGRAMMER INTERFACE
to activate the programmer interface (two way infrared communications) test.
On successful test completion, "PASS" is displayed. Otherwise, "FAIL" is displayed.
P908 SCANNER
to activate the scanner test.
When activated, the on board transducer relay is energized and de-energized.
(The transmit pulse is not supplied to the transducer terminals during this test).
P910 RELAY
Access this parameter to display the current state of the specified relay.
to alter the relay state (energized / de-energized) or enter the value
corresponding to the specific relay state desired.
values: 0 = de-energized
1 = energized
P911 mA OUTPUT VALUE
Access this parameter to display the current value of the specified mA output.
Additionally, this feature may be used to enter a desired value. The mA output is immediately
forced to the value entered, regardless of any restrictions programmed.
values: 0.000 to 25.00
P912 TRANSDUCER TEMPERATURE
Access this parameter to display the vessel temperature in °C (as monitored by the connected
ultrasonic / temperature transducer). "Err" is displayed if the transducer is not equipped with an
integral temperature sensor.
values: -50 to 150
P913 SENSOR TEMPERATURE
Access this parameter to display the vessel temperature in °C (as monitored by the connected
temperature sensor). "OPEn" is displayed if a TS-3 is not connected.
values: -50 to 150