PARAMETER SETTINGS FOR POINT # 00 (both points)
P001 Operation No entry required. (preset for
distance
).
P002 Material Enter "1" for
flat surface
).
P003 Measurement Response Enter "5" for
turbo
(17 m/s).
P004 Transducer Enter "110" for
XLS-60
.
P005 Units No entry required. (preset for
metres
.)
P006 Empty Enter "60" for transducer face to maximum distance equals
60.00 m
.
P007 Span No entry required (preset to 60.00 m.)
P100 Relay Set Up Enter "2" for
Hi and Hi Hi
alarm relays for both points.
P101 Hi Alarm Enter "29" for
29 m from Empty
(31.00 m approach distance).
P103 Hi Hi Alarm Enter "44" for
44 m from Empty
(16.00 m approach distance).
With process control equipment disabled, enter the RUN mode to monitor system performance and alarm
programming. (A Reading Measurement simulation (P920) may be performed to verify relay programming).
When satisfied with system performance and programming:
» connect the forward alarm indicator to Relay # 1.
» connect the forward drive disable controller to Relay # 2.
» connect the reverse alarm indicator to Relay # 3.
» connect the reverse drive disable controller to relay # 4.
(Note that relays are de-energized in "power off" and "alarm" conditions).
To increase Measurement Response further (if necessary), set:
P700 Max Fill Rate Enter "9999" for
9999 m/s
.
P701 Max Empty Rate Enter "9999" for
9999 m/s
.
P740 Peripheral Communications Enter "0" for
ASCII transmitter off
.
P822 Narrow Echo Filter Enter "0" for
filter off
.
P840 Short Shot Number Enter "0" for
no short shots
(nearest object outside short shot range).