PARAMETER SETTINGS FOR POINT # 00 (River side/Plant side level measurement set up)
P001 Operation Enter "1" for
level
.
P002 Material No entry required (preset for
liquid
).
P003 Measurement Response Enter "1" for
slow
(0.1 m/min).
P004 Transducer Enter "102" for
XPS-10
.
P005 Units Enter "2" for
centimetres
.
P006 Empty Enter "275" for
275.0 cm
(transducer face to Empty).
P007 Span No entry required (preset to
242.0 cm
).
P100 Relay Set Up No entry required (preset for
Hi and Lo alarms
on both points).
P101 Hi Alarm Enter "225" for
225.0 cm
(river level high alarm = 281 m).
P102 Lo Alarm Enter "25" for
25.00 cm
(river level low alarm = 279 m).
PARAMETER SETTING FOR POINT # 2 (Plant side level increase alteration).
P710 Max Fill Rate Enter "120" for
120.00 m/min (2 cm/sec)
.
PARAMETER SETTING FOR POINT # 3 (Dual Point Differential set up)
P001 Operation Enter "4" for
difference
.
PARAMETER SETTING FOR RELAY # 3 (Differential level high alarm).
P110 Relay Allocation Enter "3" for
Point 3
.
P112 Relay A Setpoint Enter "12" for alarm on at 12.00 cm differential level
P113 Relay B Setpoint Enter "9" for alarm off at 9.00 cm differential level
PARAMETER SETTINGS FOR mA OUTPUT # 1 (River level mA output set up)
P200 mA Range No entry required. (preset for
4 mA = lo, 20 mA = hi
, P001 = 1).
PARAMETER SETTINGS FOR mA OUTPUT # 2 (Differential level mA output set up)
P200 mA Range No entry required. (preset for
4 mA = lo, 20 mA = hi
, P001 = 1).
P201 mA Function Enter "1" for Point 3
P202 mA Allocation Enter "3" for
Point Number 3
P210 0/4 mA Setpoint Enter "0" for 4 mA Setpoint equals
0.00 cm
differential.
P211 20 mA Setpoint Enter "12" for 20 mA Setpoint equals
12.00 cm
differential.
With process control equipment disabled, perform a Reading Measurement simulation (P920).
When satisfied with system performance and programming:
» connect the high alarm indicator to Relay # 1.
» connect the low alarm indicator to Relay # 2.
» connect the high differential indicator to Relay # 3.
» connect the river level chart recorder to mA Output 1.
» connect the differential level chart recorder to mA Output 2.
Note that relays are de-energized in the "alarm" condition and when the DPL+ power is "off".