PARAMETER SETTINGS FOR POINT # 00 (Both Points 1 and 2)
P001 Operation Enter "1" for
level
.
P002 Material Enter "2" for
solid.
P003 Measurement Response No entry required (preset to
medium
, 1 m/min).
P004 Transducer Enter "105" for
XPS-30
.
P005 Units Enter "4" for
feet
.
P006 Empty Enter "74" for transducer face to Empty equals
74.00 ft
.
P007 Span No entry required (preset to
72.20 ft
).
P100 Relay Set Up Enter "4" for
Hi, Lo, Hi Hi, and Lo Lo
alarms.
P101 Hi Alarm Enter "68" for almost Full alarm at
68.00 ft
.
P102 Lo Alarm Enter "6" for almost Empty alarm at
6.00 ft
.
P103 Hi Hi Alarm Enter "70" for full alarm at
70.00 ft.
P104 Lo Lo Alarm Enter "4" for empty alarm at
4.00 ft
.
PARAMETER SETTINGS FOR POINT # 3 (DPA set up)
P001 Operation Enter "5" for
Dual Point Average
.
PARAMETER SETTINGS FOR RELAY # 00 (All Alarms)
P110 Relay Allocation Enter "3" for
Point 3
(average level).
After the Relay Allocation is altered, if relay trip point adjustment is required, use Relay A Setpoint
(P112) and Relay B Setpoint (P113), with the appropriate Relay Number displayed.
With process control equipment disabled, enter the RUN mode to monitor system performance and
alarm programming. Otherwise, perform a Reading Measurement simulation (P920) to verify alarm
programming.
When satisfied with system performance and programming:
» connect the near full alarm/indicator to Relay # 1.
» connect the near empty alarm/indicator to Relay # 2.
» connect the full alarm/indicator to Relay # 3.
» connect the empty alarm/indicator to Relay # 4.
(Note that relays are de-energized in "power off" and "alarm" conditions).