Connections, DIP Switches, and Jumpers
The following hardware configuration must be performed before installing the PR-300.
6.6.1 PR-300 jumper settings
The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence
is active. This allows the City Tie Box to be manually reset. On subsequent alarms the
silenceable signals will resound and the City Tie Box will be retriggered.
The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail for 0, 1
or 3 hours if this is the only system trouble.
P1
Cable connects to P3 on the Main Board
P2 & JW4
Not used. Jumper JW4 remains on board.