EasyManuals Logo

Mircom FA-301-12DDR User Manual

Mircom FA-301-12DDR
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
56
Configuration
Table 7 describes the options in the Feature Config menu.
Table 7 Feature Config menu
Feature Default
Name in the
FA-300
Configuration Utility
Description
1 Manual Signal Silence
[X] ENABLE->Default
[ ] DISABLE
Manual signal silence
Use this function to enable or
disable the SIGNAL SILENCE
button. See "9.2.2 SIGNAL
SILENCE Button" on page 44.
Command Menu - FA-300 Config - Features
2 Fire Drill
[X] ENABLE ->Default
[ ] DISABLE
Fire drill
Use this function to enable or
disable the FIRE DRILL button.
See "9.2.3 FIRE DRILL
Button" on page 44.
Command Menu - FA-300 Config - Features
3 Output Circuit Correlation
[X] DISABLE ->Def
[ ] ENABLE
Signal correlations
If enabled, the programmed
correlations (see section
11.4.4 on page 60) are
effective. If disabled, the
programmed correlations are
ignored and all the output
circuits are correlated to all the
input circuits.
Command Menu - FA-300 Config - Features
4 Waterflow/Sprinkler Retard
Operation
[X] DISABLE ->Def
[ ] ENABLE
Retard waterflow and
sprinkler circuit
If disabled, all the initiating
circuits configured as water
flow or sprinkler act as non-
verified alarms. If enabled,
retard operation is performed
for initiating circuits configured
as water flow or sprinkler.
See "9.4.5 Water Flow Alarm
(Water Flow Sensors)" on
page 46.
Command Menu - FA-300 Config - Features
5 “Aux. disconnect” disconnects
Auxiliary Alarm Relay and all
correlated relays
[ ] ENABLE
[X] DISABLE->Default
"Aux Disconnect"
disconnects prog.
relay
If enabled, the Auxiliary Alarm
Relay and all correlated relays
are disconnected when you
select “Aux Disconnect” (see
page 75). Correlated relays
include: RM312/RM306 relays
and SRM-312 relays.
If disabled, only the Auxiliary
Alarm Relay is disconnected
when you select “Aux
Disconnect” (see page 75).
Command Menu - FA-300 Config - Features
6 Signal Silence Inhibit timer
[X] DISABLE->Default
[ ] 10 SEC
[ ] 20 SEC
[ ] 30 SEC
[ ] 1 MIN
Signal silence inhibit
Use this function to inhibit the
SIGNAL SILENCE button for a
desired length of time. While
this timer is running, pressing
the SIGNAL SILENCE button
has no effect. See "9.2.2
SIGNAL SILENCE Button" on
page 44.
Manual Sig. Silence
[X] ENABLE
Fire Drill
[X] ENABLE
Opt. Ckt. Corr.
[X] DISABLE
Waterflow/Sprk. Retd
[X] DISABLE
Aux Disc Prog
[X] DISABLE
Sig-Sil. Inhibit Tmr
[X] DISABLE

Table of Contents

Other manuals for Mircom FA-301-12DDR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FA-301-12DDR and is the answer not in the manual?

Mircom FA-301-12DDR Specifications

General IconGeneral
BrandMircom
ModelFA-301-12DDR
CategoryControl Panel
LanguageEnglish

Related product manuals