65
Configuration
11.9 Clear EventLog (Command Menu)
11.10 Walk Test (Command Menu)
A walk test allows an installer to verify the initiating circuit wiring in a system. When walk test is
selected, the following screen appears:
Figure 37 Walk test confirmation
Press the ENTER button to activate the walk test and the CANCEL button to cancel the walk
test. The next screen will allow zones to be selected for walk test. Use the up and down arrow
buttons to scroll through the zones and use the left and right arrow buttons to select a zone.
Press the ENTER button when you are done with all the selections.
Figure 38 Walk test zones
The walk test is now active (see Figure 39).
Figure 39 Walk test active
The activation of any initiating circuit that has been selected for a walk test will cause the
audible indicating circuits (not strobes) to activate briefly for a number of short bursts
corresponding to the selected circuit number. If the first selected circuit is activated, the
Select the type of log to clear. Press the
ENTER button. The system confirms before
clearing logs.
Press the ENTER button to confirm or the
CANCEL button to cancel the operation.
Use this menu to clear alarm logs, general logs, or both.
-Select Log-
1 Alarm Log
2 General Log
3 All Logs
Clear all the
selected log(s)? Y
-WALK TEST ZONES-
[ ] Zone-1
-Walk test active-
Alarm:00 Trb:00