FX Series Programmable Controlers Applied Instructions 5
5-24
5.2.7 FMOV (FNC 16)
Operation:
The data stored in the source device (S) is copied to
every device within the destination range. The range
is specified by a device head address (D) and a
quantity of consecutive elements (n). If the specified number of destination devices (n)
exceeds the available space at the destination location, then only the available destination
devices will be written to.
Mnemonic Function
Operands
Program steps
SD n
FMOV
FNC 16
(Fill move)
Copies a single
data device to a
range of
destination
devices
KnX, KnY,
KnM, KnS,
T, C, D, V, Z
KnY, KnM,
KnS,
T, C, D, V, Z
K, H
)
Note:n 512
FMOV,FMOVP:7
steps
DFMOV,DFMOVP
:
13 steps
FX
1S
FX1N FX2N
FX2NC
PULSE-P
16 BIT OPERATION
32 BIT OPERATION
X0
FMOV K 0 D 0
[ S ] [ D ]
K 10
n
Note: This instruction has a special programming technique which allows it to mimic the
operation of newer applied instructions when used with older programming tools. See page 1-
5 for more details.

Table of Contents

Other manuals for Mitsubishi FX1N Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX1N Series and is the answer not in the manual?

Mitsubishi FX1N Series Specifications

General IconGeneral
Programming LanguageLadder Logic
Output TypeRelay, Transistor
Operating Temperature0 to 55°C
Power Supply100-240V AC or 24V DC
Program Capacity8K steps
Communication PortsRS-422
Data Memory8000 words
High-speed CountersUp to 6 channels
Expansion ModulesAvailable
Pulse Output2 points

Related product manuals