348
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
10 Display Module (Only FX3UC-32MT-LT)
10.15 Cassette (Memory Cassette Transfers)
• Result and measures to take:
- The transfer is not executed if a "PLC is running" message
appears.
In this case, set the PLC to the STOP state, then perform step 3)
described above.
- The transfer is not executed if a "Transfer failed" message
appears.
In this case, turn the power off, check the memory cassette
connection, then attempt the operation again from the first step.
- The transfer is not executed if a "Memory Cassette is write-
protected" message displays.
In this case, turn the power OFF, set the memory cassette
PROTECT switch to OFF, then attempt the operation again from
the first step.
- A "Transfer completed" message appears when the transfer is
completed.
When this message appears, press [OK] or [ESC] to display the
"Cassette screen".
5) Press [ESC] to display the "menu screen".
PCLingsirunn
()
RAMCas e t tse
Wr i et
Tran f re
f
s
ai eld
Memo y C
i
r
s
port
asse te
w
t
ri et- cetde
s
()
RAMCas e t tse
Wr i et
Tran f re
c
s
om lpeetd