318
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.18 Details of buffer memory
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
9.18.14 Remote device station input (output) data area
[BFM #144 (90h) to #159 (9Fh) and #208 (D0h) to #223 (DFh)]
This area is used to access the input (output) data in the remote device station indirectly using the FROM and
TO instructions or directly using the buffer memory specification.
Access is enabled to only BFMs for which remote device stations are actually connected.
(The TO instruction is ignored and the FROM instruction returns "0" for a station number to which a remote
I/O station is connected.)
Station No.
BFM#
Remote input area Remote output area
Station No.49 144 208
Station No.50 145 209
...
...
...
Station No.63 158 222
Station No.64 159 223