73
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
1 Outline
1.14 Selection Calculation Example 3 for System Configuration
1
Outline
2
External
Dimensions
3
Generic
Specifications
4
Power Supply
Specifications
5
Input
Specifications
6
Output
Specifications
7
Examples of
Wiring for
Various Uses
8
Terminal Block
9
CC-Link/LT
Master FX
3UC
(LT only)
10
Display module
FX
3UC
(LT only)
- Extension power supply unit side
3) Restriction for the number of connectable units
a) Expansion board
There is no problem since the components have not changed.
b) Special function unit/block
There is no problem since the components have not changed.
c) Other restrictions
The new configuration is as follows due to insertion of an extension power supply unit between the
FX
2NC-16EYR-T and the FX2NC-16EYR-T:
- One FX
2NC-16EYR-T unit is connected to the main unit.
There is no problem with this configuration since it satisfies the restriction for the
number of connectable units (1 units).
- One FX
2NC-16EYR-T unit is connected to the extension power supply unit.
There is no problem with this configuration since it satisfies the restriction for the
number of connectable units (5 units).
a)Supplier side
FX
3UC
-1PS-5V 1A (1000mA)
b)Consumer side
100mA
220mA
290mA
5V DC power supply capacity and current consumption
"a)Supplier side" - "b)Consumer side" = 1000mA - 290mA =710mA
≥
0mA
FX
2NC
-16EYR-T
FX
2NC
-4AD
FX
2NC
-CNV-IF
FX
2N
-10PG
FX
2N
-2LC
FX
2N
-16CCL-M
50mA
50mA
0mA
120mA
70mA
0mA
There is no problem since the total current consumption is less than the
capacity "1A (1000mA)" supplied by the extension power supply unit.
OK!!
OK!!
OK!!
OK!!
OK!!
The restrictions for the number of input/output points, the restriction for the 5V DC power supply
capacity and the restriction for the number of connectable units are satisfied and the
configuration is valid when an extension power supply unit is added.