EasyManuals Logo

Netafim NMC-64 User Manual

Netafim NMC-64
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
User & Installation Maunal Software
The cooling / humidification program is used to keep the greenhouse temperature
below a set value and / or the humidity above a set value. Each program can be set to
maintain temperature or humidity as its first priority.
There are 5 Cooling programs available with 2 periods in each program. The periods
can be defined to overlap thus creating “dynamic” cooling or humidification.
Different temp. and humidity sensors can be connected to each program.
Program – choose the required program 1 to 5.
Status – define whether the programs first priority is maintaining temperature or
humidity:
Cooling – the program’s priority is temperature. If the two periods are
overlapping, and there are different settings in each period dynamic cooling
will take place.
Example:
Period 1 is set between 06:00 to 16:00, Above temp is 30
o
, Below RH
is 90%, On is 00:00:30 and Off is 00:05:00.
Period 2 is set between 08:00 to 18:00, Above temp is 40
o
, Below RH
is 80%, On is 00:01:00 and Off is 00:10:00.
Time is 07:00, the temperature is 35
o
and the humidity is 65% the
cooling valve will be open for 30 seconds every 5 minutes.
Time is 12:00, the temperature is 30
o
and the humidity is 65% the
cooling valve will be open for 30 seconds every 5 minutes.
Time is 10:00, the temperature is 40
o
and the humidity is 50% the
cooling valve will be open for 1 minute every 10 minutes.
Time is 15:00, the temperature is 35
o
and the humidity is 60% the
cooling valve will be open for 45 seconds every 7-½ minutes.
Time is 17:00, the temperature is 35
o
and the humidity is 60% the
cooling valve will not be opened.
If the temperature is 35
o
and the humidity is 85% the cooling valve will
not be opened.
If the time is relevant only for a certain period only its settings will define
operation.
If humidity is above the lowest value of the two periods cooling will not take
place.
Humidification - the program’s priority is humidity. If the two periods are
overlapping, and there are different settings in each period dynamic
humidification will take place.
29

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Netafim NMC-64 and is the answer not in the manual?

Netafim NMC-64 Specifications

General IconGeneral
BrandNetafim
ModelNMC-64
CategoryController
LanguageEnglish

Related product manuals