User & Installation Maunal Software
3.4 ALARM SETTING
ALARM SETTING
Description Irri. Fert. Delay
Mm:ss
Alarm
Active
High Flow
Low Flow
No Flow
D. Ch. Leak
D. Ch. Fault
Ext. Pause
EC High/Fail
EC Low
Ph High
PH low/Fail
STOP
CONT
STOP
STOP
PAUSE
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
STOP
IRRIG
STOP
STOP
STOP
STOP
STOP
01:00
01:00
30:00
01:00
01:00
01:00
01:00
01:00
01:00
01:00
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
The setting table enables to define required response for faults recognized by the
NMC-64:
STOP – Stop Irrigation and/or Dosing for current valve (or valve group) and
continue to the next valve.
CONT – Continue Irrigation and/or Dosing for the valve (or group of valve) that
caused the alarm.
Delay (mm:ss) – Define the period the fault must be measured for before the
NMC-64 will take action.
Alarm Active – Define whether the alarm output should be activated due to the
relevant alarm.
An alarm will be generated on the NMC-64 screen even if the NMC has been
set to continue or the alarm output has been set as not active (or not defined
at all).