3.2 HISTORY
Every alarm from the last reset will have a record on this table (Up to 250 alarms).
HISTORY
Message Date Time
1
2
Shortage ? 08/Sep 10:01:34
Relay Card No. 1 Fail 23/Mar 13:35:44
3.3 ALARM DEFINITION
ALARM DEFINITION
Water Fill up (min)
Water Leak (m3 / Gal.)
Water Leak Period (hh:mm)
Dosing Channel Leak Delay (s)
Dosing Channel Leak (Pulse)
Delta EC Low
Delta EC High
Delta pH Low
Delta pH High
Missing Pulses For No Flow
Max Consecutive Flow Alarms
No. Of Short Circ. To Pause
Short Circuit Control
1
10.000
00:30
15
10
0.50
0.50
0.50
0.50
3
3
3
300
Water Fill Up (Min.) - Time for line fill up. The system will ignore high flow and will
not generate a High Flow alarm during this period.
Water Leak (m3 / Gal.) - Quantity of water to trigger a water leak alarm. The
quantity is either in m3 or gallon depending on the choice of volume units.
Water Leak Period (hh:mm) - Time frame to measure the Water Leak quantity. If
it takes the system more time than indicated here to measure the Water Leak
quantity the system will not generate an alarm.
Dosing Channel Leak Delay (s) – Delay after dosing channel is stopped before
the system starts measuring Dosing Channel Leak. This feature is usually used to
cope with problems regarding hydraulic pumps that work with fertilizer meters.