Hardware Installation and Setup
3-24
Part 1120130
E 2011 Nordson Corporation
Connecting and Programing the Pump for Remote
Control
Complete the Wiring and Programming instructions below to remotely
monitor and run the pumps.
Wiring
To use the motor run status monitoring capability, connect wiring from the
parent machine to the appropriate terminals on I/O connectors on right panel
of the electrical enclosure. See Figure 3-14 for the location of I/O connectors.
Refer to Table 3-2 for the terminal numbers that correspond to each
input/output
NOTE: The relay contact between terminals
-17X21:25/-17X21:26,-17X21:27/-17X21:28,-17X21:29/-17X21:30,-17X21:3
1/-17X21:32 are normally open. When the motor is running, these contacts
should close..
Programming
Use the keypad located on each pump drive inside the electrical enclosure to
set up the pump run status monitoring. Refer to Changing a Motor Drive
Parameter in Section 6, Troubleshooting, for a more detailed procedure for
changing a motor drive parameter.
1. Press ENT until I-O is displayed.
2. Press ENT again to access the I/O parameters.
3. Press the arrow keys until parameter r2 is displayed.
4. Press ENT to access this parameter.
5. Press the arrow keys until rUn is displayed.
6. Press ENT to save this value.
7. Press ESC twice to return to the monitoring mode.