Conveyor Speed Percent Adjust
Conveyor Speed Percent Adjust works as follows, using the example in
Figure 8-8:
The nominal conveyor speed is 16 ft/min. As long as the conveyor speed
stays within the dead band (± 2%, or ± 0.2 ft/min., or 15.68−16.32 ft/min.)
nothing happens. If the conveyor speed increases past 16.32 ft/min. then
flows are increased linearly until at 18 ft/min. both flow settings have been
increased by 10%.
If the conveyor speed decreases below 9.8 ft/min. and keeps decreasing,
then flows are decreased linearly until at 8 ft/min. both flow settings have
been decreased by 20%. If the conveyor speed goes above 18 ft/min. the
adjustment stays at 10%; if it goes below 8 ft/min. the adjustment stays at
20%.
To turn the Conveyor Speed Percent Adjust function off, touch the
Enable/Disable selection box.
OFF
ON
Flow-rate Air
or Powder Flow
% Adjust Limit
% Atomizing Air
or Pattern Air
Enable/
Disable
Fast
Nominal
Slow
Dead Band
Global
% Adjust
Conveyor
% Adjust
Speed % Flow
% Speed
Atomizing Air
or Pattern Air
% Adjust Limit
% Flow-rate Air
or Powder Flow
Figure 8-8 Percent Adjust Screen