Operating Parameters
B-15
Part 1120277_01
E 2012 Nordson Corporation
33 Standard Input 4
Description: Control options that determine the function of input 4.
Value: 0 – Input Disabled
1 – Standby On/Off
2 – Heaters On/Off
3 – Motor Enable/Disable
4 – Hose/Gun 1 Enable/Disable
5 – Hose/Gun 2 Enable/Disable
6 – Hose/Gun 3 Enable/Disable
7 – Hose/Gun 4 Enable/Disable
8 – Hose/Gun 5 Enable/Disable
9 – Hose/Gun 6 Enable/Disable
11 – Motor 2 Enable/Disable (DuraBlue D50 and D100 melters
only)
13 - Automatic Fill Timer 1
14 - Automatic Fill Timer 2 (DuraBlue D50 and D100 melters
only)
Resolution: 1
Default Value: 4
Format: —
Use: Multiple inputs can be set to the same input value. After one or
more inputs that have the same input value are energized, the
input functionality will not be considered inactive (off) until all of
the inputs with the same input value are de-energized (multiple
inputs set to the same input value are logical ORed.).
NOTE: Parameter 78, Automatic Fill Timer,mustbesettoa
value of 1 or greater in order to use option 13 or 14. Output
option 6, Alert, can be used to signal when the Automatic Fill
Timer expires.