Reading or Editing Operating Parameters
Regardless of whether a parameter's value is editable or not, the procedure
for accessing each parameter in order to read or edit its current value is the
same.
To read or edit a parameter
1. Switch the melter on.
The melter performs a start-up check.
2. Press the Setup key.
The left display flashes parameter 1.
3. Use the numeric keypad to enter the number of the desired parameter.
Refer to Table 3-6 for a complete list of parameters.
NOTE: If you incorrectly enter the parameter number, press the
Clear/Reset key to return to parameter 1 and then re-enter the correct
parameter number.
When you have finished entering the one- or two-digit parameter number,
the right display indicates the parameter's current value.
4. Do one of the following:
S If the value is noneditable, refer to Monitoring the Melter in Section 4,
Operation.
S If the value is editable go to step 5.
5. Press the Enter key.
The right display flashes.
6. Use the keypad to enter the desired numeric setpoint or control option
into the right display. Refer to Appendix B, Operating Parameters,for
information about the numeric value or control option choices for each
parameter.
NOTE: If the keypad has no affect on the right display, the melter is
password protected. You must enter a valid password before you can
edit parameters. Refer to Entering the Melter Password in Section 4,
Operation.