Sensor Input Setting Range, Indication Range, Control Range
A-13
Appendices
Input type
Specifica-
tions
Temperature
range
Input temperature range Control range
0 99 to 850 (°C)/ 99 to 1,500 (°F) 119 to 870 (°C)/139 to 1,540 (°F)
1 0.0 to 199.9 (°C)/0.0 to 199.9 (°F) 20.0 to 219.9 (°C)/40.0 to 239.9 (°F)
2 99 to 99 (°C)/ 99 to 99 (°F) 119 to 119 (°C)/139 to 139 (°F)
3 0 to 200 (°C)/0 to 200 (°F) 20 to 220 (°C)/40 to 240 (°F)
Pt100
4 0 to 400 (°C)/0 to 400 (°F) 20 to 420 (°C)/ 40 to 440 (°F)
5 99 to 500 (°C)/ 99 to 900 (°F) 199 to 520 (°C)/139 to 940 (°F)
6 0.0 to 199.9 (°C)/0.0 to 199.9 (°F) 20.0 to 219.9 (°C)/40.0 to 239.9 (°F)
7 99 to 99 (°C)/ 99 to 99 (°F) 119 to 119 (°C)/139 to 139 (°F)
8 0 to 200 (°C)/0 to 200 (°F) 20 to 220 (°C)/40 to 240 (°F)
Multi-input
(thermocouple/
platinum
resistance
thermometer)
models
(control mode
switch 5: ON)
JPt100
9 0 to 400 (°C)/0 to 400 (°F) 20 to 420 (°C)/40 to 440 (°F)
The default is 2 for thermocouple input, 3 for platinum resistance thermometer input, 1 for thermistor
input, and 0 for multi-input (thermocouple/platinum resistance thermometer) models.
The applicable standards for each of the above input ranges are as follows:
K, J, T, N, R: JIS C1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
Element-compatible thermistors (6 K (0°C)), (30 K (0°C)), 550 (200°C)), 4 K (200°C)):
JIS C1611-1995
The input indication range is the range that can be displayed for the control range (99 to 1999).
* The PV display is shown in units of 1°C/°F, but the control range is determined up to one decimal
point.