Appendices
A-8
Appendices
Parameter Operation Lists
Operation Level
Parameters
Mode
indicators/
displayed
text
Setting (monitor) value Default Unit
Set
value
Process value
Sensor input indication range
EU
Set point SP mode
SP lower limit to SP upper limit
0 EU
Alarm value 1 ALM mode 1 to 7: 0 to input setting range full scale
8: Input setting range lower-limit value to
input setting range upper-limit value
0 EU
Alarm value 2 ALM2
mode
1 to 7: 0 to input setting range full scale
8: Input setting range lower-limit value to
input setting range upper-limit value
0 EU
Input shift value IS mode
L99 to H99 (99 to 99)
H0 EU
Manual reset value IS mode
L99 to H99 (99 to 99)
H0 EU
0: AT cancel AT execute/cancel IS mode
at
1: AT execute
0 None
0: Latch OFF Alarm 1 latch status IS mode
a1
1: Latch ON
0 None
0: Latch OFF Alarm 2 latch status IS mode
a2
1: Latch ON
0 None

Table of Contents

Other manuals for Omron E5CSV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CSV and is the answer not in the manual?

Omron E5CSV Specifications

General IconGeneral
Setting MethodDigital setting using front panel keys
Dimensions48 x 48 x 78 mm (W x H x D)
Number of Control Outputs1
Control MethodON/OFF control or PID control
Input TypesThermocouple
Supply Voltage100 to 240 VAC
Output TypeRelay or Voltage (for driving SSR)
Display7-segment digital display
Mounting MethodPanel mounting
Setting Resolution0.1 °C or 1 °C
Power Supply Voltage100 to 240 VAC
Ambient Operating Humidity25% to 85% RH
Ambient Operating Temperature-10 to 55°C (with no icing or condensation)