Loading...
Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
b50
Speed Control 3 Notch
Filter Attenuation Lev-
el
0 to 40 dB
0
Availa-
ble
dB
page
6-26
4-2-8
Parameter r (Speed Control 4)
Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
r43
Speed Control 4
Speed Command Fil-
ter
0.000 to 5.000 s
0.02
Availa-
ble
s
page
6-26
r44
Speed Control 4
Speed Detection Filter
0.000 to 0.100 s
0.005
Availa-
ble
s
page
6-26
r45
Speed Control 4 P
Proportional Gain
0.1 to 200.0
10
Availa-
ble
-
page
6-26
r46
Speed Control 4 I Inte-
gral Time
0.001 to 9.999 s
999: Disable
0.1
Availa-
ble
s
page
6-26
r47
Speed Control 4 FF
Gain
0.00 to 99.99 s
0
Availa-
ble
s
page
6-26
r48
Speed Control 4 Out-
put Filter
0.000 to 0.100 s
0.002
Availa-
ble
s
page
6-26
r49
Speed Control 4 Notch
Filter Resonance Fre-
quency
1 to 500 Hz
200
Availa-
ble
Hz
page
6-26
r50
Speed Control 4 Notch
Filter Attenuation Lev-
el
0 to 40 dB
0
Availa-
ble
dB
page
6-26
4 Parameter List