EasyManuals Logo

Omron M1 Series User Manual

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
1-4
Restrictions
Availability of Functions by Individual Control Method
Available functions are restricted depending on the selected control method.
“15:PM Vector control without speed and pole position sensor” and “16:PM Vector control with speed
and pole position sensor” can be set to only 1st motor control.
Function name
1st Drive Control Selection(F42)/2nd Drive Control Selec-
tion(A14)
0: IM V/f control
1: IM Dynamic torque
vector control
3: IM V/f control with
speed sensor
4: IM Dynamic torque vector
control with speed sensor
5: IM Vector control without
speed sensor
6: IM Vector control with
speed sensor
15: PM Vector control without
speed and pole position sensor
16: PM Vector control with
speed and pole position sensor
Torque boost manual adjustment
Avail-
able
N/A
Avail-
able
Avail-
able
N/A N/A N/A N/A
Invalidation of automatic voltage control
(AVR)
Avail-
able
N/A
A
vail-
able
Avail-
able
N/A N/A N/A N/A
Energy-saving operation mode
Avail-
able
Avail-
able
Avail-
able
Avail-
able
N/A
Avail-
able
N/A N/A
Motor sound (Tone) N/A N/A N/A N/A
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Invalidation of slip compensation
Avail-
able
N/A N/A N/A N/A N/A N/A N/A
DC injection braking
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Avail-
able
N/A N/A
Startup DC injection braking
Avail-
able
Avail-
able
Avail-
able
Avail-
able
N/A N/A N/A N/A
Frequency pull-in restart
Avail-
able
Avail-
able
N/A N/A
Avail-
able
N/A N/A N/A
Current limiter, instantaneous overcur-
rent limiting
Avail-
able
Avail-
able
Avail-
able
Avail-
able
N/A N/A N/A N/A
Torque limit
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Torque control N/A N/A N/A N/A
Avail-
able
Avail-
able
N/A
Avail-
able
Torque bias N/A N/A N/A N/A
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Automatic speed control (ASR), Notch
filter
N/A N/A N/A N/A
Avail-
able
Avail-
able
Avail-
able
Avail-
able
Zero speed control N/A N/A N/A N/A
Avail-
able
Avail-
able
N/A
Avail-
able
1 Overview
1-24
M1 Series Standard Type User's Manual (I669)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
Input Voltage200-240V AC
Output Voltage3-phase 200 to 240 VAC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus RTU
EnclosureIP20
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m
Frequency Range0.5-400 Hz
Storage Temperature-20°C to +65°C