Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H438
Feedback Value Com-
parison Signal Of
f Lev-
el
0.0 to 100.0%
100.0 - %
page
7-123
H439
Feedback Value Com-
parison Signal On
Level
0.0 to 100.0%
0.0 - %
page
7-123
H440
Free Run Stop Restart
Allowable Time
0.0 to 30.0 s
30.0 - s
page
7-60
H441
Free Run Stop Restart
Operation Selection
1: Starting with matching fre-
quency
2: Starting with active match-
ing frequency
2 - -
page
7-60
H442
Slip compensation
Function Selection
0: Disable
1: Enable
0
Availa-
ble
-
page
5-16
4-2-6
Parameter A (Motor 2 Parameter)
Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
A01
2nd Maximum Output
Frequency
5.0 to 590.0 Hz
60.0 - Hz
page
5-19
A02 2nd Base Frequency
5.0 to 590.0 Hz
50.0 - Hz
page
5-19
A03
2nd Rated Voltage at
Base Frequency
80 to 240 V: AVR operation
(200 V class series)
160 to 500 V: AVR operation
(400 V class series)
200
- V
page
5-19
4 Parameter List
4-135
M1 Series Standard Type User's Manual (I669)
4-2 List of Parameters by Group
4
4-2-6 Parameter A (Motor 2 Parameter)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
Input Voltage200-240V AC
Output Voltage3-phase 200 to 240 VAC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus RTU
EnclosureIP20
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m
Frequency Range0.5-400 Hz
Storage Temperature-20°C to +65°C