When braking load at deceleration is a constant speed
How to apply a braking load Allowable average loss
Thermal braking resistance
value
Braking
l
oa
d (kW)
Tim
e
Braking time (s) × Motor capacity (kW)
Electronic Thermal for Braking
Resistor Discharging Ca
pacity
(F50) =
× Motor capacity (kW)
%ED(%)
100
Electronic Thermal for Braking
Resistor Allowable Avera
ge
Loss (F51) =
Additional Information
When a braking resistor capable of outputting a temperature detection signal is applied, set
“9: EXT (external trip)” to one of Input Terminal [DI1] Function Selection to Input Terminal
[DI7] Function Selection (E50 to E55, E98, E99), and connect the temperature detection sig-
nal of the braking resistor
.
Even if there is actually little temperature rise, the electronic thermal sometimes is activated
and the overheating protection dbH alarm is generated depending on the braking resistor
specifications. Check the specifications of the braking resistor and set its parameter.
5 Basic Settings
5-76
M1 Series Standard Type User's Manual (I669)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
Input Voltage200-240V AC
Output Voltage3-phase 200 to 240 VAC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus RTU
EnclosureIP20
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m
Frequency Range0.5-400 Hz
Storage Temperature-20°C to +65°C

Related product manuals