In the Modbus Mapping Endian Selection (H396), set the endian you want to use.
The Modbus Mapping Endian Selection H396 setting is enabled independent of the Modbus Mapping
Function Selection (H355) setting.
Parameter No. Function name Data Default data Unit
H396
Modbus Mapping Endian
Selection
0: Big endian
1: Little endian
2: Special endian
0 -
Byte order of single-word data
Relationship between single-word data bits and bytes
Bit 8 to 15 7 to 0
Byte MSB byte LSB byte
Order of data during Modbus communication
Send/Receive byte or-
der
Big endian Little endian Special endian
1 MSB byte LSB byte MSB byte
2 LSB byte MSB byte LSB byte
Byte order of double-word data
Relationship between double-word data bits and bytes
Bit 24 to 31 16 to 23 8 to 15 7 to 0
Byte MSB byte Data 1 Data 2 LSB byte
Order of data during Modbus communication
Send/Receive byte or-
der
Big endian Little endian Special endian
1 MSB byte LSB byte Data 2
2 Data 1 Data 2 LSB byte
3 Data 2 Data 1 MSB byte
4 LSB byte MSB byte Data 1
Executable function codes
This function is enabled only for the function codes listed below.
Other function codes will be processed in big endian.
Function code
03 hex Read from multiple holding registers
06 hex Write to a holding register
10 hex Write to multiple holding registers
17 hex Read/Write from/to multiple holding registers
8 Communications Functions
8-26
M1 Series Standard Type User's Manual (I669)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
Input Voltage200-240V AC
Output Voltage3-phase 200 to 240 VAC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus RTU
EnclosureIP20
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m
Frequency Range0.5-400 Hz
Storage Temperature-20°C to +65°C

Related product manuals