Alarm
code
Alarm
sub-
code
Name Description  Check point and remedy reference
(0LU)
 
Inverter over-
load
(1) The ambient tem-
perature exceeds the
inverter specification
range
Measure the ambient temperature.
Reduce the ambient temperature such
as by improving the air flow to the pan-
el.
 
(2) 1st Manual Torque
Boost V
oltage (F09*)
too high
Check 1st Manual Torque Boost V
oltage
(F09*) and readjust so that this does not stall
even if data is lowered.
Adjust F09*.
 
(3) Short acceleration/
deceleration time
Recalculate acceleration/deceleration torque
and acceleration/deceleration time required
from the moment of inertia of the load and
acceleration/deceleration time.
Lengthen the acceleration/deceleration
time (F07, F08, E10 to E15, H56).
 
(4) High load Measure the output current.
Reduce the load (use the Overload ear-
ly warning 2 Level (OL2) (E34), and re-
duce the load before an overload oc-
curs.) (During winter
, the load may in-
crease.)
Decrease the Carrier Frequency (F26).
Enable Overload Prevention Control
(H70)
 
(5) The airflow path is
blocked
Check that there is sufficient installation
space.
Ensure sufficient installation space.
Check for fin clogging.
Clean.
 
(6) Reduced fan airflow
because of the cooling
fan service life or of
damage
Check the cumulative run time of the cooling
fan. (Refer to 7-8-13 Cooling Fan Life W
arn-
ing Signal (WAF)
on page 7-99.)
Replace the cooling fan.
Visually check that the cooling fan is operat-
ing correctly.
Replace the cooling fan.
 
(7) Long output wiring,
with high leakage cur-
rent
Measure the leakage current
Insert an output circuit filter (OFL).
(0PL)
 
Output phase
loss detection
(1) Disconnected invert
output wiring
Measure the output current.
Replace the output wiring.
 
(2) Motor windings bro-
ken
Measure the output current.
Replace the motor.
 
(3) Loose inverter out-
put terminal connection
Check if inverter output terminal screws are
loose.
Tighten to the recommended tightening
torque.
9 Troubleshooting
9-21
M1 Series Standard Type User's Manual (I669)
9-1 Alarm Display and Remedies
9
9-1-2 Alarm Code List