EasyManua.ls Logo

Omron M1 Series

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Inspec-
tion cat-
egory
Inspec-
tion item
Inspection point
Inspection
frequency
Inspection method Criteria Meter
Daily
Peri-
odic
1 year
2 years
Main cir-
cuit
General Perform megger
check
(Between main
circuit terminals
and ground termi-
nal).
Required
Disconnect I/O wires
from the inverter
main circuit terminal
block and remove
the control terminal
block PCB. Then, af-
ter removing the
short-circuit bar for
switching the inverter
built-in filter function,
measure using a
megger the resist-
ance between the
ground terminal and
the short-circuited
terminals L1/R, L2/S,
L3/T, U, V, W, P(+),
P1, N(-) and DB.
5 MΩ min. 500-VDC
class
megger
Check for loose
bolts and screws.
Required
Retighten loose bolts
and screws.
No faults
Check each part
for traces of over-
heating.
Required
Perform visual in-
spection.
No faults
Conduc-
tors/
wires
Check for distort-
ed conductors.
Required
Perform visual in-
spection.
No faults
Check for broken
cable sheaths.
Required
Terminal
Blocks
Check for dam-
age.
Required
Perform visual in-
spection.
No faults
Smooth-
ing ca-
pacitor
*1
Check that there
is no liquid leak-
age.
Required
Perform visual in-
spection.
No faults Capacity
meter
Check that the
safety valve does
not come out and
that there is no
bulge.
Required
Relay Check for chatter-
ing sound during
operation.
Required
Perform acoustic in-
spection.
No faults
Check for rough
contact surface.
Required
Perform visual in-
spection.
No faults
10 Maintenance and Inspection
10-4
M1 Series Standard Type User's Manual (I669)

Table of Contents

Related product manuals