4 Controller Setup
4-12
NJ-series CPU Unit Software User’s Manual (W501)
Basic I/O Units
The following settings are made in the Unit Information of the Basic I/O Units.
Access point
Setting
group
Description
Set
values
Default
Update tim-
ing
Changes in
RUN mode
Unit Informa-
tion
Note Set the
informa-
tion for
each
slot.
Basic Input
Unit Input
Response
Time
Sets the input response time (ON
response time = OFF response
time) of the Basic Input Unit. You
can set no filter or you can set the
value in increments from 0 to 32 ms.
You can increase the value to
reduce chattering and the effects of
external noise. If you decrease the
value, shorter input pulses are
received (but the pulses must be
longer than the task period).
No filter
0.5 ms,
1 ms,
2 ms,
4 ms,
8 ms,
16 ms,
or
32 ms
8 ms When power
is turned ON
or the CPU
Unit is reset
Not allowed.