12 Troubleshooting
12-14
NJ-series CPU Unit Software User’s Manual (W501)
Errors Related to Tasks
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info
60020000 hex Task Execu-
tion Timeout
Task execution
exceeded the time-
out detection time.
The timeout detection time set-
ting is too short.
The task period setting is too
short.
A user program is too large.
The number of times that pro-
cessing is repeated is larger
than expected.
Task Priority Error
Frequent Event Task Execution
page 12-23
60030000 hex I/O Refresh-
ing Timeout
Error
Consecutive I/O
refresh failures
occurred during the
primary periodic
task or periodic task
period.
The task period setting is too
short.
Task Priority Error for Periodic
Tasks and Event Tasks
There are too many Units and
slaves that perform I/O refresh
in the task period.
Frequent Event Task Execution
page 12-24
60040000 hex Insufficient
System Ser-
vice Time
Error
The specified sys-
tem service execu-
tion time could not
be obtained.
There was not sufficient time to
execute the tasks and tag data
link service.
The system service execution
interval is too short or the sys-
tem service execution time ratio
is too long in the System Ser-
vice Monitoring Settings.
page 12-25
60010000 hex Task Period
Exceeded
Task execution was
not completed dur-
ing the set task
period for the pri-
mary periodic task
or a periodic task.
The task period setting is too
short.
A user program is too large.
The number of times that pro-
cessing is repeated is larger
than expected.
Task Priority Error for Periodic
Tasks and Event Tasks
Frequent Event Task Execution
page 12-26
60050000 hex Task Period
Exceeded
Task execution was
not completed dur-
ing the set task
period for the pri-
mary periodic task
or fixed periodic
task.
The task period setting is too
short.
A user program is too large.
The number of times that pro-
cessing is repeated is larger
than expected.
Task Priority Error for Periodic
Tasks and Event Tasks
F
r
equen
t Ev
ent T
ask Ex
e
cution
page 12-27

Table of Contents

Other manuals for Omron NJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ Series and is the answer not in the manual?

Omron NJ Series Specifications

General IconGeneral
Program CapacityUp to 128 MB
SD Card SlotYes
Power Supply Voltage24 VDC
Motion ControlYes
USB Ports1
Operating Temperature0°C to 55°C
Communication InterfacesEthernet/IP, EtherCAT, USB
Safety FunctionOptional
Storage Temperature-20°C to 75°C
Communication PortsUSB
DimensionsVaries by model
WeightVaries by model