12 Troubleshooting
12-30
NJ-series CPU Unit Software User’s Manual (W501)
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 12-7.
Event name Illegal User Program/Controller Configurations and Setup Event code 10250000 hex
Meaning The upper limit of the usable memory was exceeded or the user program or Controller Configurations and Setup is cor-
rupted.
Source PLC Function Module Source details None Detection
timing
At download,
power ON, or
Controller reset
Error attributes Level Major fault Recovery Cycle the power
supply or reset
the Controller.
Log category System
Effects User program Stops. Operation Stops.*
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The upper limit of the data size was
exceeded.
If an event on restrictions on the num-
ber of items used occurred at the
same time as this event, correct the
user program and settings so that the
number of items used is not exceeded
and then download the data again.
None
The main memory capacity was
exceeded.
If an event on restrictions on the num-
ber of items used did not occur at the
same time as this event, perform the
Clear All Memory operation, cycle the
power supply, and then confirm that
this event was cleared. If it was
cleared, reduce the size of the proj-
ect, e.g., by sharing programming,
and then download the project again.
Non-volatile memory is deteriorating
or has failed.
If this error persists even after you
implement the above two corrections,
replace the CPU Unit.
Attached
information
None
Precautions/
Remarks
None

Table of Contents

Other manuals for Omron NJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NJ Series and is the answer not in the manual?

Omron NJ Series Specifications

General IconGeneral
Program CapacityUp to 128 MB
SD Card SlotYes
Power Supply Voltage24 VDC
Motion ControlYes
USB Ports1
Operating Temperature0°C to 55°C
Communication InterfacesEthernet/IP, EtherCAT, USB